RITTER Slide-in Type Switchgear GT 4D
DESCRIPTION
12 kV compact switchgear with double busbar system, circuit breakers with slide-in or fixed mounted design and busbar connectors or load-break disconnectors.
Design
Metal enclosed, air insulated, factory assembled and type tested. Compartmentalization is made between the cubicles as well as between busbar-, slide-in and cable compartment sections.
Application range
Circuit-breaker switchgear can be used for distribution substations in grid-, industrial- and power supply plants and are applicable for the switching of transformers, motors, generators, capacitors and transmission lines.
Cubicle styles
Incoming feeder, outgoing feeder, metering- and busbar coupling; bussection- and busriser panels with motorized loadbreak panels with motorized loadbreak switches and withdrawable circuit breakers.
PRODUCT DATA
TECHNICAL DATA
Rated voltage
Busbar current
Branch current
Peak current
Shorttime current
Short circuit duration
Arc resistance
12 kV
Up to
3150 A
Up to
3150 A
Up to
80 kA
Up to
31,5 kA
3s
1s
DIMENSIONS
Current
Width
Depth
Height
1250 A
600 mm
1420 mm
2500 mm
1600-2500 A
800 mm
1420 mm
2500 mm
Outline GT4D